Air
Handling Unit General Selection Table |
|
GSSC |
unit |
1V1 |
1V2 |
1V3 |
1V4 |
2V2 |
2V3 |
2V4 |
3V3 |
3V4 |
4V3 |
4V4 |
| R22CoolingCapacity |
kW |
142,0 |
178,0 |
219,0 |
277,0 |
356,0 |
438,0 |
554,0 |
657,0 |
831,0 |
876,0 |
1108,0 |
| Compressor
power input |
kW |
30,9 |
38,8 |
48,0 |
60,4 |
77,6 |
96,0 |
120,8 |
144,0 |
181,2 |
192,0 |
241,6 |
| Cooled water vol. flow rate |
m/h |
24,4 |
30,6 |
37,7 |
47,6 |
61,2 |
75,3 |
95,3 |
113,0 |
142,9 |
150,7 |
190,6 |
| Evaporator Pressure Loss |
kPa |
59 |
60 |
60 |
60 |
60 |
61 |
61 |
62 |
62 |
62 |
62 |
| R4O7CCoolingCapacity |
kW |
146,3 |
183,4 |
225,6 |
285,4 |
366,8 |
451,2 |
570,7 |
676,8 |
856,1 |
902,5 |
1141,5 |
| Compressor power input |
kW |
30,9 |
38,8 |
48,0 |
60,4 |
77,6 |
96,0 |
120,8 |
144,0 |
181,2 |
192,0 |
241,6 |
| Cooled
water vol. flow rate |
m/h |
25,2 |
31,5 |
38,8 |
49,1 |
63,1 |
77,6 |
98,2 |
116,4 |
147,2 |
155,2 |
196,3 |
| Evaporator Pressure Loss |
kPa |
59 |
60 |
60 |
60 |
60 |
61 |
61 |
62 |
62 |
62 |
62 |
| Nr. of compressors |
Pcs |
1 |
2 |
3 |
4 |
| Nr.
of currents |
Pcs |
1 |
2 |
3 |
4 |
| Nr.
of states |
% |
Continuous
capacity control system: In the range of 25%-100%
Per compressor |
| Length |
mm |
3000 |
3000 |
3000 |
3000 |
3800 |
3800 |
3800 |
3400 |
3400 |
3500 |
3500 |
| Width |
mm |
1100 |
1100 |
1100 |
1100 |
1100 |
1100 |
1100 |
1800 |
1800 |
1800 |
1800 |
| Height |
mm |
1400 |
1400 |
1400 |
1400 |
1800 |
1800 |
1800 |
1900 |
1900 |
2000 |
2000 |
| Weight |
Kg |
950
|
1050
|
1400
|
1550
|
2000
|
2700
|
3000
|
4100
|
4500
|
5500
|
6100
|
|
Sound Pressure Level |
dB(A) |
54 |
55 |
56 |
57 |
57 |
58 |
59 |
60 |
61 |
62 |
63 |
|
|
*Specified
sound levels are sound pressure levels in 10 m free-range.
*Performance is under aforementioned conditions:
*Water temperature 12/7 c - condenser water
inlet/outlet temperatures 27/32 C
|
|
|